While doing layout of a plant we need to provide access to valves for operating and maintenance. Here we will list out the distances need to be maintained for the same:
1. For vertical stem valves:
Vertical distance from Grade to valve handles top edge – 1100mm to 1300mm
2nd choice acceptable- 600 mm to 1100mm
Valves can be placed over access area with chain pulley -minimum head clearance needed – 2200 mm

2. For horizontal stem valves:
Vertical distance from Grade to valve handles centre line – 1100mm to 1400mm
2nd choice acceptable- 600 mm to 1100mm
Valve chain wheel height approx – 900mm
Valve distance to be maintained if from outside grating – 500 mm
Minimum width of access way for maintenance of valve- 1070 mm

2. Clear headroom:
Clear headroom under structure/piping inside operating area – 2200 mm

Leave a Reply